Hi all,
I have a Multiplus, with AGM batteries and Venus Gx, AC coupled to an Enphase grid tie system. Got the ESS installed on the Multi, and have run in to some issues. The most annoying one is that the Multiplus charger does not reset back to bulk after discharging to minimum SOC.
So during the day the panels do charge the batteries, and during the night the batteries get discharged to Minimum SOC. But the charger never resets back to Bulk. So after reaching Float the first time, it remains in float forever. This will cause lead acid batteries to fail prematurely.
After many testings I did realize the Multiplus charger only gets reset when the grid fails(inverter goes in to island mode).
So the fix was to set the ESS to toggle the relay 1 via the "Generator start/stop" feature, every day at 6:00am for 1 minute. Plugged the relay output to Auxiliary 2 input on the Multiplus and ran enough instances of the Programmable relay and general flag assistant to make the Multi go in to island mode every day.
Now I am trying to figure how to set a timer for the power assist feature not to work until the batteries get fully charged. I don't like that on cloudy days the multi keep interrupting the charge and discharging the batteries when the panels get obscured.
Best regards,
Alex
Dominican Republic