Pls change minimum configuration steps from 5% to 1% for the ESS Minimum SoC (until grid fails).
Tia
Br
Mike
This site is now in read-only archive mode. Please move all discussion, and create a new account at the new Victron Community site.
I'm also needing this, because my battery is 1860Ah 48V and 5% is like 4,5kwh. That's like 6h with my load of ~700W.
I would like to set my SOC to 13% instead of 15%.
Im pretty sure your can set any percentage using mqtt
EDIT: Just tried it, and your can!
W/yourdevice/settings/0/Settings/CGwacs/BatteryLife/MinimumSocLimit
JSON
{"value": 13}
Yes, you can but it is not even displayed correctly in the GX...I am also using 13% SoC, which technically works, but is displayed as 15% in the GX Settings-Menu