In alarm rules I can not make ONLY a ""LOW SOC"" alarm.
I can make a low and high SOC alarm only.
This way I get to many unwatned email, from every time the battery is full.
This site is now in read-only archive mode. Please move all discussion, and create a new account at the new Victron Community site.
@BenM you can set the high alarm above 100% like 105% and set the clear high alarm below 104%.
It should never trigger the high alarm, only on low.
thanks I will try.
Funny that you can program a value that is outside normal range!!