TAB: General System frequency 50Hz Shore current 20.0 A Overruled by remote checked Dynamic current limiter unchecked External current sensor connected (see manual) checked State of charge when Bulk finished 85.0 % Battery capacity 100 Ah Charge efficiency 0.96 TAB: Grid Country / grid code standard UK: G98/1 March 2019, G99/1 May 2018 LOM detection AC input 1 Type B (grid code compliant) start P(f) at 50.40 Hz start delay for p(F) 0.08 s Droop for p(F) 10.0 % Use Aux1 (if available) as disable FeedIn signal checked Reactive power regulation Use a fixed Cos Phi Filter time for reactive power 3.3 s Cos phi at point 1 1.00 TAB: Inverter PowerAssist unchecked Inverter output voltage 230 V Inverter DC shut-down voltage 44.00 V Inverter DC restart voltage 48.00 V Low DC alarm level 48.00 V Do not restart after short-circuit (VDE 2510-2 safety) unchecked enable AES unchecked TAB: Charger Enable charger checked Weak AC input unchecked Stop after excessive bulk unchecked Lithium batteries checked Use equalization (tubular plate traction battery curve) unchecked Charge curve Fixed Absorption voltage 52.00 V Float voltage 51.00 V Charge current 35 A Repeated absorption time 1.00 Hr Repeated absorption interval 7.00 Days Absorption time 1 Hr TAB: Virtual switch TAB: Usage Virtual switch usage Do not use VS TAB: Assistants TAB: Assistant Configuration ESS (Energy Storage System) (size:1709) *) System uses LiFePo4 with other type BMS (This can be either a BMS connected via CAN bus or a BMS system in which the batteries are protected from high/low cell voltages by external equipment.) *) The battery capacity of the system is 100 Ah. *) Sustain voltage 48.00 V. *) Cut off voltage for a discharge current of: 0.005 C= 46.00 V 0.25 C= 46.00 V 0.7 C= 46.00 V 2 C= 46.00 V *) Inverting is allowed again when voltage rises 1.20 V above cut-off(0). *) The solar converter will start reducing its output power at 50.20 Hz. Output power will be reduced to minimum when the frequency is 52.70 Hz. The converter will disconnect when the frequency is higher than 53.00 Hz. *) Total installed PV inverter power is 1500 Watts. Total installed PV panel power is 1500 Watts. *) Relevant VEConfigure settings: - Battery capacity 100 Ah. - PowerAssist unchecked - Lithium batteries checked - Dynamic current limiter unchecked - Storage mode unchecked Total size of all assistants including the required (hidden) system assistants is: 1782