TAB: General System frequency 50Hz Shore current 10.0 A Overruled by remote checked Dynamic current limiter unchecked External current sensor connected (see manual) unchecked State of charge when Bulk finished 95.0 % Battery capacity 146 Ah Charge efficiency 0.95 TAB: Grid Country / grid code standard None: (feeding energy from DC to grid not allowed) Accept wide input frequency range (45-65 Hz) checked AC low switch mains off 180 V AC low switch mains on 187 V AC high switch mains on 265 V AC high switch mains off 270 V UPS function checked TAB: Inverter PowerAssist checked Assist current boost factor 2.0 Inverter output voltage 230 V Ground relay checked Inverter DC shut-down voltage 44.00 V Inverter DC restart voltage 48.00 V Low DC alarm level 48.00 V Do not restart after short-circuit (VDE 2510-2 safety) unchecked enable AES checked Load for starting AES mode 92 W Offset for ending AES mode 46 W AES type modified sine wave TAB: Charger Enable charger checked Weak AC input unchecked Stop after excessive bulk unchecked Lithium batteries checked Configured for VE.Bus BMS unchecked Charge curve Fixed Absorption voltage 56.80 V Float voltage 54.00 V Charge current 70 A Repeated absorption time 1.00 Hr Repeated absorption interval 7.00 Days Absorption time 1 Hr TAB: Virtual switch TAB: Usage Virtual switch usage Do not use VS TAB: Assistants TAB: Assistant Configuration PV Inverter support (size:793) *) The solar converter will start reducing its output power at 50.20 Hz. Output power will be reduced to minimum when the frequency is 52.70 Hz. The converter will disconnect when the frequency is higher than 53.00 Hz. *) Total installed PV inverter power is 5000 Watts. Total installed PV panel power is 5200 Watts. Total size of all assistants including the required (hidden) system assistants is: 866