TAB: GeneralSystem frequency 50Hz Shore current 10.0 A Overruled by remote checked Dynamic current limiter unchecked State of charge when Bulk finished 85.0 % Battery capacity 200 Ah Charge efficiency 1.00 TAB: Grid Country / grid code standard None: (feeding energy from DC to grid not allowed) Accept wide input frequency range (45-65 Hz) checked AC low switch mains off 180 V AC low switch mains on 187 V AC high switch mains on 265 V AC high switch mains off 270 V UPS function checkedTAB: Inverter PowerAssist checked Assist current boost factor 2.0 Inverter output voltage 230 V Ground relay checked Inverter DC shut-down voltage 37.20 V Inverter DC restart voltage 43.60 V Low DC alarm level 43.60 V Do not restart after short-circuit (VDE 2510-2 safety) unchecked enable AES uncheckedTAB: Charger Enable charger checked Weak AC input unchecked Stop after excessive bulk unchecked Lithium batteries unchecked Storage mode unchecked Use equalization (tubular plate traction battery curve) unchecked Charge curve Fixed Absorption voltage 55.50 V Float voltage 55.10 V Charge current 26 A Repeated absorption time 0.50 Hr Repeated absorption interval 1.00 Days Absorption time 8 HrTAB: Virtual switch TAB: Usage Virtual switch usage Do not use VS TAB: Assistants TAB: Assistant Configuration PV Inverter support (size:757) *) The solar converter will start reducing its output power at 50.10 Hz. Output power will be reduced to minimum when the frequency is 51.00 Hz. The converter will disconnect when the frequency is higher than 53.00 Hz. *) Total installed PV inverter power is 1500 Watts. Total installed PV panel power is 1500 Watts. programmable relay (size:175) *) Use secondary programmable relay K1. *) Set relay off *) in case of a general system failure. *) when SOClower than 80%. programmable relay (1) (size:30) *) Use secondary programmable relay K1. *) Set relay on *) when SOChigher than 99%. Total size of all assistants including the required (hidden) system assistants is: 1044